The PVA-2P500 class-D
amplifier is a 2 x 500 W audio amplifier for evacuation
purposes. It can be operated from both the mains and a DC supply. The output
voltage is galvanically insulated and is constantly monitored for ground fault.
An energy saving mode and temperature-controlled fans reduce energy consumption
and noise levels. The control and monitoring functions are performed via CAN
bus. This amplifier is designed for operation in an emergency evacuation
system. The amplifiers are usually controlled via a controller and configured
using IRIS-Net.
The power amplifier has the
following features:
• Floating 100 V or 70 V
power outputs.
• High efficient amplifier
blocks in class-D technology.
• Outputs idling and short
circuit-protected.
• Mains operation
120-240 V (50/60 Hz) and/or 24 V DC emergency backup.
• Electronically balanced
inputs.
• Temperature monitoring
function.
• Processor control of all
functions.
• Monitoring of the processor
system via watchdog circuit.
• Non-volatile FLASH memory
for configuration data.
• Internal monitoring
function.
• Integrated audio relays.
• Line monitoring function.
• Pilot tone and ground fault
monitoring function via PVA‑4CR12 controller or PVA‑4R24 router.
Technical Specification
|
Electrical
|
Rated
load impedance (output power)
|
100
V
|
20
Ω (500 W)
|
70
V
|
10
Ω (500 W)
|
Rated
output power, 1 kHz, THD ≤ 1%
|
2 x
500 W1
|
Rated
input voltage
|
+6
dBu
|
Max.
RMS voltage swing, 1 kHz, THD ≤ 1%, without load
|
100
V
|
110
V
|
70
V
|
78
V
|
Voltage
gain, ref. 1 kHz, fixed
|
70
V
|
33.2
dB
|
100
V
|
36.2
dB
|
Maximum
load capacitance
|
2
µF
|
Input
level, max.
|
+18
dBu (9.75 Vrms)
|
Frequency
response, ref. 1 kHz, rated load, -3 dB
|
50
Hz to 25 kHz
|
Input
impedance, active balanced
|
20
kΩ
|
Signal-to-noise
ratio (A-weighted)
|
>
104 dB
|
Output
noise (A-weighted)
|
<
-62 dBu
|
Crosstalk,
ref. 1 kHz
|
<
-85 dB
|
|
Output
stage topology
|
Class-D,
transformer, floating
|
|
Power
requirements
|
|
Power
supply
|
Mains:
115-240 VAC ±10%, 50/60 Hz2
Battery:
21-32 VDC
|
|
Power
consumption
|
Pmax
- 3dB * / idle **/ Standby 230VAC, 50Hz: 700W / 21W / 1.9W
120VAC,
60Hz: 745W / 18W / 1.5W
24VDC,
60Hz: 735W / 16W / 1.5W
*
Alarm, ** No audio (pilot tone)
|
|
Inrush
current
|
2A
|
|
Inrush
current, after five-second power cycle
|
1.3A
|
|
Main
Fuse
|
T6.3A
(internally)
|
|
DC
Fuse
|
30A
(internally)
|
|
Ground
Fault
|
R
< 50 kΩ
|
|
CAN
BUS port
|
2 x
RJ-45, 10 to 500 kbit/s
|
|
Protection
|
Audio
input level limiter, RMS output power limiter, high temperature, DC, short
circuit,
|
|
Cooling
|
Front-to-rear,
temperature- controlled fans
|
|
Environmental
|
|
Operating
temperature
|
-5 °C
to +45 °C (+23 °F to +113 °F)
|
|
Storage
temperature
|
-40
°C to +70 °C (-40 °F to +158 °F)
|
|
Humidity
(non-condensing)
|
5%
to 90%
|
|
Altitude
|
Up
to 2000 m
|
|
Mechanical
|
|
Dimensions
(HxWxD)
|
88 mm
x 483 mm x 375 mm (2RU)
|
|
Weight
(net)
|
16.5
kg
|
|
Mounting
|
Standalone;
19 in. rack
|
|
Color
|
Black
with silver
|
|